IEC 61850 UE01 UE02
CSMSQI1
VMMXU1
RESVMMXU1
VSMSQI1
PEMMXU1
XRGGIO130 o
FMMXU1
● = available in the device variant, o = optionally available in the device variant
2.3 Point list for REU615 Ver.4.0 UE01-02
2.3.1 Indications
Table 3: Explanations of the indications table columns
Column name Description
IEC 61850
name
Original IED data object identification. Described in the IEC 61850 format as
Logical Device.Logical Node and thereafter .Data Object.Data Attribute. Logical
Node is the same as the application function block name.
SA name The signal may have a defined label that is visible for example in ACT.
Description Short description of the signal. See the application function block documentation
for more details.
Value Meaning of the value states.
2.3.1.1 CommonData1
Table 4: CommonData1
BitA
RegA IEC 61850 name SA name Description Values
CTRL.LLN0
2720 170.00 .Loc.stVal - Remote/Local state 0/1=Rem/Loc
2721 170.01 .LocRem.stVal.Station - Station state 1=Station
DR.RDRE1
2722 170.02 .RcdMade.stVal - DR recording made 1=Made
2723 170.03 .mcd
LD0.LLN0
2726 170.06 .SetSeld.stVal Settings reserved 1=Reserved
2727 170.07 .mcd
2728 170.08 .SetChg.stVal Settings changed 1=Changed
2729 170.09 .mcd
1MRS757057 B Section 2
Modbus data mappings
REU615 15
Point List Manual