2.3.1.2 LD0.LEDPTRC1 Global conditioning
Table 5: LD0.LEDPTRC1 Global conditioning
BitA RegA IEC 61850 name SA name Description Values
LD0.LEDPTRC1
2736 171.00 .Str.general - Global start 1=Start
2737 171.01 .mcd
2738 171.02 .Op.general - Global operate 1=Operate
2739 171.03 .mcd
2.3.1.3 LD0.TRPPTRC1 Protection trip conditioning (1)
Table 6: LD0.TRPPTRC1 Protection trip conditioning (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.TRPPTRC1
2740 171.04 .Op.general - Op.Input signal 1=Operate
2741 171.05 .mcd
2742 171.06 .Tr.general - Trip output signal 1=Trip
2743 171.07 .mcd
2.3.1.4 LD0.TRPPTRC2 Protection trip conditioning (2)
Table 7: LD0.TRPPTRC2 Protection trip conditioning (2)
BitA
RegA IEC 61850 name SA name Description Values
LD0.TRPPTRC2
2744 171.08 .Op.general - Op.Input signal 1=Operate
2745 171.09 .mcd
2746 171.10 .Tr.general - Trip output signal 1=Trip
2747 171.11 .mcd
2.3.1.5 LD0.CMMXU1 Phase current limit supervision (1)
Table 8: LD0.CMMXU1 Phase current limit supervision (1)
BitA
RegA IEC 61850 name SA name Description Values
LD0.CMMXU1
2752 172.00 .HiAlm.stVal HIGH_ALARM High alarm 1=Alarm
2753 172.01 .mcd
2754 172.02 .HiWrn.stVal HIGH_WARN High warning 1=Warning
2755 172.03 .mcd
2756 172.04 .LoWrn.stVal LOW_WARN Low warning 1=Warning
Table continues on next page
Section 2 1MRS757057 B
Modbus data mappings
16 REU615
Point List Manual