BitA RegA IEC 61850 name SA name Description Values
2757 172.05 .mcd
2758 172.06 .LoAlm.stVal LOW_ALARM Low alarm 1=Alarm
2759 172.07 .mcd
2.3.1.6 LD0.RESVMMXU1 Residual voltage limit supervision (1)
Table 9: LD0.RESVMMXU1 Residual voltage limit supervision (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.RESVMMXU1
2764 172.12 .HiAlm.stVal HIGH_ALARM High alarm 1=Alarm
2765 172.13 .mcd
2766 172.14 .HiWrn.stVal HIGH_WARN High warning 1=Warning
2767 172.15 .mcd
2.3.1.7 LD0.LEDGGIO1 Indication LED states
Table 10: LD0.LEDGGIO1 Indication LED states
BitA
RegA IEC 61850 name SA name Description Values
LD0.LEDGGIO1
2768 173.00 .SPCSO1.stVal - LED 1 state 0/1=Off/On
2769 173.01 .SPCSO2.stVal - LED 2 state 0/1=Off/On
2770 173.02 .SPCSO3.stVal - LED 3 state 0/1=Off/On
2771 173.03 .SPCSO4.stVal - LED 4 state 0/1=Off/On
2772 173.04 .SPCSO5.stVal - LED 5 state 0/1=Off/On
2773 173.05 .SPCSO6.stVal - LED 6 state 0/1=Off/On
2774 173.06 .SPCSO7.stVal - LED 7 state 0/1=Off/On
2775 173.07 .SPCSO8.stVal - LED 8 state 0/1=Off/On
2776 173.08 .SPCSO9.stVal - LED 9 state 0/1=Off/On
2777 173.09 .SPCSO10.stVal - LED 10 state 0/1=Off/On
2778 173.10 .SPCSO11.stVal - LED 11 state 0/1=Off/On
2779 173.11 < reserved > 0
2.3.1.8 LD0.TCSSCBR1 Trip circuit supervision (1)
Table 11: LD0.TCSSCBR1 Trip circuit supervision (1)
BitA
RegA IEC 61850 name SA name Description Values
LD0.TCSSCBR1
2780 173.12 .CirAlm.stVal ALARM Supervision alarm 1=Alarm
2781 173.13 .mcd
1MRS757057 B Section 2