2.3.1.9 LD0.TCSSCBR2 Trip circuit supervision (2)
Table 12: LD0.TCSSCBR2 Trip circuit supervision (2)
BitA RegA IEC 61850 name SA name Description Values
LD0.TCSSCBR2
2782 173.14 .CirAlm.stVal ALARM Supervision alarm 1=Alarm
2783 173.15 .mcd
2.3.1.10 LD0.VMMXU1 Phase voltage limit supervision (1)
Table 13: LD0.VMMXU1 Phase voltage limit supervision (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.VMMXU1
2784 174.00 .HiAlm.stVal HIGH_ALARM High alarm 1=Alarm
2785 174.01 .mcd
2786 174.02 .HiWrn.stVal HIGH_WARN High warning 1=Warning
2787 174.03 .mcd
2788 174.04 .LoWrn.stVal LOW_WARN Low warning 1=Warning
2789 174.05 .mcd
2790 174.06 .LoAlm.stVal LOW_ALARM Low alarm 1=Alarm
2791 174.07 .mcd
2.3.1.11 CTRL.DCSXSWI1 Disconnector 1 mom position
Table 14: CTRL.DCSXSWI1 Disconnector 1 mom position
BitA
RegA IEC 61850 name SA name Description Values
CTRL.DCSXSWI1 POSITION
2792 174.08 .Pos.stVal.Close - Close bit 1=Close
2793 174.09 .Pos.stVal.Open - Open bit 1=Open
2794 174.10 .Pos.stVal.Fault - Fault bit 1=Pos(00/11)
2.3.1.12 CTRL.DCSXSWI2 Disconnector 2 mom position
Table 15: CTRL.DCSXSWI2 Disconnector 2 mom position
BitA
RegA IEC 61850 name SA name Description Values
CTRL.DCSXSWI2 POSITION
2795 174.11 .Pos.stVal.Close - Close bit 1=Close
2796 174.12 .Pos.stVal.Open - Open bit 1=Open
2797 174.13 .Pos.stVal.Fault - Fault bit 1=Pos(00/11)
Section 2 1MRS757057 B
Modbus data mappings
18 REU615
Point List Manual

Table of Contents