BitA RegA IEC 61850 name SA name Description Values
3031 189.07 .mcd
3032 189.08 .Op.general OPERATE General operate 1=Operate
3033 189.09 .mcd
2.3.1.25 LD0.ARCSARC1 Fault arc protection, stage 1
Table 28: LD0.ARCSARC1 Fault arc protection, stage 1
BitA RegA IEC 61850 name SA name Description Values
LD0.ARCSARC11
3156 197.04 .FADet.stVal ARC_FLT_DET Arc detected 1=Detected
3157 197.05 .mcd
LD0.ARCPTRC11
3158 197.06 .Op.general OPERATE Stage operate 1=Operate
3159 197.07 .mcd
2.3.1.26 LD0.ARCSARC2 Fault arc protection, stage 2
Table 29: LD0.ARCSARC2 Fault arc protection, stage 2
BitA
RegA IEC 61850 name SA name Description Values
LD0.ARCSARC21
3160 197.08 .FADet.stVal ARC_FLT_DET Arc detected 1=Detected
3161 197.09 .mcd
LD0.ARCPTRC21
3162 197.10 .Op.general OPERATE Stage operate 1=Operate
3163 197.11 .mcd
2.3.1.27 LD0.ARCSARC3 Fault arc protection, stage 3
Table 30: LD0.ARCSARC3 Fault arc protection, stage 3
BitA
RegA IEC 61850 name SA name Description Values
LD0.ARCSARC31
3164 197.12 .FADet.stVal ARC_FLT_DET Arc detected 1=Detected
3165 197.13 .mcd
LD0.ARCPTRC31
3166 197.14 .Op.general OPERATE Stage operate 1=Operate
3167 197.15 .mcd
1MRS757057 B Section 2
Modbus data mappings
REU615 23
Point List Manual