2.3.1.28 LD0.SEQRFUF1 Fuse failure protection
Table 31: LD0.SEQRFUF1 Fuse failure protection
BitA RegA IEC 61850 name SA name Description Values
LD0.SEQRFUF1
2876 179.12 .Str.general FUSEF_U Start 1=Start
2877 179.13 .mcd
2878 179.14 .Str3Ph.general FUSEF_3PH 3-phase start 1=Start
2879 179.15 .mcd
2.3.1.29 CTRL.CCRDIF1 Current circuit failure detection
Table 32: CTRL.CCRDIF1 Current circuit failure detection
BitA RegA IEC 61850 name SA name Description Values
CTRL.CCRDIF1
2860 178.12 .Alm.stVal ALARM Alarm 1=Alarm
2861 178.13 .mcd
2862 178.14 .Op.general FAIL Failure operate 1=Operate
2863 178.15 .mcd
2.3.1.30 LD0.PHPTOV1 Phase overvoltage protection (1)
Table 33: LD0.PHPTOV1 Phase overvoltage protection (1)
BitA
RegA IEC 61850 name SA name Description Values
LD0.PHPTOV1
2912 182.00 .Str.general START General start 1=Start
2913 182.01 .mcd
2914 182.02 .Str.phsA phsA start 1=Start
2915 182.03 .mcd
2916 182.04 .Str.phsB phsB start 1=Start
2917 182.05 .mcd
2918 182.06 .Str.phsC phsC start 1=Start
2919 182.07 .mcd
2920 182.08 .Op.general OPERATE General operate 1=Operate
2921 182.09 .mcd
Section 2 1MRS757057 B
Modbus data mappings
24 REU615