2.3.1.36 LD0.NSPTOV2 Negative-sequence overvoltage protection (2)
Table 39: LD0.NSPTOV2 Negative-sequence overvoltage protection (2)
BitA RegA IEC 61850 name SA name Description Values
LD0.NSPTOV2
2998 187.06 .Str.general START General start 1=Start
2999 187.07 .mcd
3000 187.08 .Str.phsA phsA start 1=Start
3001 187.09 .mcd
3002 187.10 .Str.phsB phsB start 1=Start
3003 187.11 .mcd
3004 187.12 .Str.phsC phsC start 1=Start
3005 187.13 .mcd
3006 187.14 .Op.general OPERATE General operate 1=Operate
3007 187.15 .mcd
2.3.1.37 LD0.PHPTUV1 Phase undervoltage protection (1)
Table 40: LD0.PHPTUV1 Phase undervoltage protection (1)
BitA
RegA IEC 61850 name SA name Description Values
LD0.PHPTUV1
2944 184.00 .Str.general START General start 1=Start
2945 184.01 .mcd
2946 184.02 .Str.phsA phsA start 1=Start
2947 184.03 .mcd
2948 184.04 .Str.phsB phsB start 1=Start
2949 184.05 .mcd
2950 184.06 .Str.phsC phsC start 1=Start
2951 184.07 .mcd
2952 184.08 .Op.general OPERATE General operate 1=Operate
2953 184.09 .mcd
2.3.1.38 LD0.PHPTUV2 Phase undervoltage protection (2)
Table 41: LD0.PHPTUV2 Phase undervoltage protection (2)
BitA
RegA IEC 61850 name SA name Description Values
LD0.PHPTUV2
2954 184.10 .Str.general START General start 1=Start
2955 184.11 .mcd
2956 184.12 .Str.phsA phsA start 1=Start
Table continues on next page
1MRS757057 B Section 2
Modbus data mappings
REU615 27