2.3.1.41 LD0.ROVPTOV2 Residual overvoltage protection (2)
Table 44: LD0.ROVPTOV2 Residual overvoltage protection (2)
BitA RegA IEC 61850 name SA name Description Values
LD0.ROVPTOV2
2980 186.04 .Str.general START General start 1=Start
2981 186.05 .mcd
2982 186.06 .Op.general OPERATE General operate 1=Operate
2983 186.07 .mcd
2.3.1.42 LD0.ROVPTOV3 Residual overvoltage protection (3)
Table 45: LD0.ROVPTOV3 Residual overvoltage protection (3)
BitA RegA IEC 61850 name SA name Description Values
LD0.ROVPTOV3
2984 186.08 .Str.general START General start 1=Start
2985 186.09 .mcd
2986 186.10 .Op.general OPERATE General operate 1=Operate
2987 186.11 .mcd
2.3.1.43 LD0.SECRSYN1 Synchrocheck (1)
Table 46: LD0.SECRSYN1 Synchrocheck (1)
BitA
RegA IEC 61850 name SA name Description Values
LD0.SECRSYN1
3128 195.08 .SynPrg SYNC_INPRO Synch. in progress 1=In progress
3129 195.09 .mcd
3130 195.10 .FailCmd CMD_FAIL_AL Close request fail 1=Failed
3131 195.11 .mcd
3132 195.12 .FailSyn CL_FAIL_AL Close cmd fail 1=Failed
3133 195.13 .mcd
2.3.1.44 LD0.OLATCC1 On-load tap changer controller
Table 47: LD0.OLATCC1 On-load tap changer controller
BitA
RegA IEC 61850 name SA name Description Values
LD0.OLATCC1
3136 196.00 .TapOpR.stVal RAISE_OWN Raise command 1=Raise
3137 196.01 .mcd
3138 196.02 .TapOpL.stVal LOWER_OWN Lower command 1=Lower
Table continues on next page
1MRS757057 B Section 2
Modbus data mappings
REU615 29