BitA RegA IEC 61850 name SA name Description Values
3139 196.03 .mcd
3140 196.04 .TapOpErr.stVal ALARM Alarm 1=Alarm
3141 196.05 .mcd
3172 198.04 .EndPosR.stVal - Block raise 1=Raise
3173 198.05 .mcd
3174 198.06 .EndPosL.stVal - Block lower 1=Lower
3175 198.07 .mcd
3176 198.08 .LTCBlkAHi.stVal BLKD_I_LOD Over current blocking 1=Block
3177 198.09 .mcd
3178 198.10 .LTCBlkVLo.stVal BLKD_U_UN Under voltage blocking 1=Block
3179 198.11 .mcd
3180 198.12 .LTCRnbk.stVal RNBK_U_OV Raise volt.runback block 1=Block
3181 198.13 .mcd
3182 198.14 .LTCBlkCirA.stVal BLKD_I_CIR High circ.current block 1=Block
3183 198.15 .mcd
3184 199.00 .LTCBlkSt.stVal BLKD_LTCBLK External blocking 1=Block
3185 199.01 .mcd
3186 199.02 .ErrParTra.stVal PAR_FAIL Parallel failure detected 1=Failure
3187 199.03 .mcd
3188 199.04 .ParOp.stVal PARALLEL Parallel or single op. 1=Parallel
3189 199.05 .mcd
3190 199.06 .Auto.stVal AUTO Auto or manual op. 1=Auto
3191 199.07 .mcd
2.3.1.45 LD0.FRPFRQ1 Frequency protection (1)
Table 48: LD0.FRPFRQ1 Frequency protection (1)
BitA
RegA IEC 61850 name SA name Description Values
LD0.FRPTRC1
3040 190.00 .Str.general START Stage 1 start 1=Start
3041 190.01 .mcd
LD0.FRPTOF1 Overfrequency
3042 190.02 .Op.general OPR_OFRQ Operate 1=Operate
3043 190.03 .mcd
LD0.FRPTUF1 Underfrequency
3044 190.04 .Op.general OPR_UFRQ Operate 1=Operate
3045 190.05 .mcd
LD0.FRPFRC1 Frequency gradient
3046 190.06 .Op.general OPR_FRG Operate 1=Operate
3047 190.07 .mcd
Section 2 1MRS757057 B
Modbus data mappings
30 REU615
Point List Manual