2.3.1.50 LD0.FRPFRQ6 Frequency protection (6)
Table 53: LD0.FRPFRQ6 Frequency protection (6)
BitA RegA IEC 61850 name SA name Description Values
LD0.FRPTRC6
3080 192.08 .Str.general START Stage 6 start 1=Start
3081 192.09 .mcd
LD0.FRPTOF6 Overfrequency
3082 192.10 .Op.general OPR_OFRQ Operate 1=Operate
3083 192.11 .mcd
LD0.FRPTUF6 Underfrequency
3084 192.12 .Op.general OPR_UFRQ Operate 1=Operate
3085 192.13 .mcd
LD0.FRPFRC6 Frequency gradient
3086 192.14 .Op.general OPR_FRG Operate 1=Operate
3087 192.15 .mcd
2.3.1.51 LD0.LSHDPFRQ1 Load shedding - instance 1
Table 54: LD0.LSHDPFRQ1 Load shedding - instance 1
BitA
RegA IEC 61850 name SA name Description Values
LD0.LSHDPTRC1
3088 193.00 .Str.general START Stage start 1=Start
3089 193.01 .mcd
3090 193.02 .Op.general OPERATE Stage operate 1=Operate
3091 193.03 .mcd
3092 193.04 .RestLodStr.general ST_REST Start of restore 1=Start
3093 193.05 .mcd
3094 193.06 .RestLodOp.general RESTORE Restore the load 1=Restore
3095 193.07 .mcd
2.3.1.52 LD0.LSHDPFRQ2 Load shedding - instance 2
Table 55: LD0.LSHDPFRQ2 Load shedding - instance 2
BitA
RegA IEC 61850 name SA name Description Values
LD0.LSHDPTRC2
3096 193.08 .Str.general START Stage start 1=Start
3097 193.09 .mcd
3098 193.10 .Op.general OPERATE Stage operate 1=Operate
3099 193.11 .mcd
Table continues on next page