2.3.1.55 LD0.LSHDPFRQ5 Load shedding - instance 5
Table 58: LD0.LSHDPFRQ5 Load shedding - instance 5
BitA RegA IEC 61850 name SA name Description Values
LD0.LSHDPTRC5
3120 195.00 .Str.general START Stage start 1=Start
3121 195.01 .mcd
3122 195.02 .Op.general OPERATE Stage operate 1=Operate
3123 195.03 .mcd
3124 195.04 .RestLodStr.general ST_REST Start of restore 1=Start
3125 195.05 .mcd
3126 195.06 .RestLodOp.general RESTORE Restore the load 1=Restore
3127 195.07 .mcd
2.3.1.56 LD0.MAPGAPC1 Multipurpose analog protection function (1)
Table 59: LD0.MAPGAPC1 Multipurpose analog protection function (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.MAPGAPC1
3142 196.06 .Op.general OPERATE Stage operate 1 = Operate
3143 196.07 .mcd
3144 196.08 .Str.general START Stage start 1 = Start
3145 196.09 .mcd
2.3.1.57 LD0.MAPGAPC2 Multipurpose analog protection function (2)
Table 60: LD0.MAPGAPC2 Multipurpose analog protection function (2)
BitA
RegA IEC 61850 name SA name Description Values
LD0.MAPGAPC2
3146 196.10 .Op.general OPERATE Stage operate 1 = Operate
3147 196.11 .mcd
3148 196.12 .Str.general START Stage start 1 = Start
3149 196.13 .mcd
1MRS757057 B Section 2
Modbus data mappings
REU615 35
Point List Manual