2.3.1.62 LD0.XGGIO130 Physical I/O states (BIO card X130)
Table 65: LD0.XGGIO130 Physical I/O states (BIO card X130)
BitA RegA IEC 61850 name SA name Description Values
LD0.XGGIO130
3280 205.00 .Ind1.stVal X130-Input 1 State 0/1=Off/On
3281 205.01 .mcd
3282 205.02 .Ind2.stVal X130-Input 2 State 0/1=Off/On
3283 205.03 .mcd
3284 205.04 .Ind3.stVal X130-Input 3 State 0/1=Off/On
3285 205.05 .mcd
3286 205.06 .Ind4.stVal X130-Input 4 State 0/1=Off/On
3287 205.07 .mcd
3288 205.08 .Ind5.stVal X130-Input 5 State 0/1=Off/On
3289 205.09 .mcd
3290 205.10 .Ind6.stVal X130-Input 6 State 0/1=Off/On
3291 205.11 .mcd
3264 204.00 .SPCSO1.stVal X130-Output 1 State 0/1=Off/On
3265 204.01 .mcd
3266 204.02 .SPCSO2.stVal X130-Output 2 State 0/1=Off/On
3267 204.03 .mcd
3268 204.04 .SPCSO3.stVal X130-Output 3 State 0/1=Off/On
3269 204.05 .mcd
2.3.1.63 CTRL.DCXSWI1 Controllable discon. 1 mom position data
Table 66: CTRL.DCXSWI1 Controllable discon. 1 mom position data
BitA
RegA IEC 61850 name SA name Description Values
CTRL.DCXSWI1 POSITION
3472 217.00 .Pos.stVal.Close - Close bit 1=Close
3473 217.01 .Pos.stVal.Open - Open bit 1=Open
3474 217.02 .Pos.stVal.Fault - Fault bit 1=Pos(00/11)
3475 217.03 .Pos.stSeld - Control selected 1=Selected
CTRL.DCCILO1
3476 217.04 .EnaOpn.stVal ENA_OPEN Open enabled 1=Enabled
3477 217.05 .EnaCls.stVal ENA_CLOSE Close enabled 1=Enabled
CTRL.DCXSWI1
3478 217.06 .BlkOpn.stVal BLK_OPEN Open blocked 1=Blocked
3479 217.07 .mcd
3480 217.08 .BlkCls.stVal BLK_CLOSE Close blocked 1=Blocked
Table continues on next page
1MRS757057 B Section 2
Modbus data mappings
REU615 37
Point List Manual