BitA RegA IEC 61850 name SA name Description Values
3481 217.09 .mcd
3482 217.10 .ItlByPss.stVal ITL_BYPASS Interlock bypass 1=Bypass
3483 217.11 .mcd
2.3.1.64 CTRL.DCXSWI2 Controllable discon. 2 mom position data
Table 67: CTRL.DCXSWI2 Controllable discon. 2 mom position data
BitA RegA IEC 61850 name SA name Description Values
CTRL.DCXSWI2 POSITION
3484 217.12 .Pos.stVal.Close - Close bit 1=Close
3485 217.13 .Pos.stVal.Open - Open bit 1=Open
3486 217.14 .Pos.stVal.Fault - Fault bit 1=Pos(00/11)
3487 217.15 .Pos.stSeld - Control selected 1=Selected
CTRL.DCCILO2
3488 218.00 .EnaOpn.stVal ENA_OPEN Open enabled 1=Enabled
3489 218.01 .EnaCls.stVal ENA_CLOSE Close enabled 1=Enabled
CTRL.DCXSWI2
3490 218.02 .BlkOpn.stVal BLK_OPEN Open blocked 1=Blocked
3491 218.03 .mcd
3492 218.04 .BlkCls.stVal BLK_CLOSE Close blocked 1=Blocked
3493 218.05 .mcd
3494 218.06 .ItlByPss.stVal ITL_BYPASS Interlock bypass 1=Bypass
3495 218.07 .mcd
2.3.1.65 CTRL.ESXSWI1 Controllable earth switch 1 mom position
Table 68: CTRL.ESXSWI1 Controllable earth switch 1 mom position
BitA
RegA IEC 61850 name SA name Description Values
CTRL.ESXSWI1 POSITION
3496 218.08 .Pos.stVal.Close - Close bit 1=Close
3497 218.09 .Pos.stVal.Open - Open bit 1=Open
3498 218.10 .Pos.stVal.Fault - Fault bit 1=Pos(00/11)
3499 218.11 .Pos.stSeld - Control selected 1=Selected
CTRL.ESCILO1
3500 218.12 .EnaOpn.stVal ENA_OPEN Open enabled 1=Enabled
3501 218.13 .EnaCls.stVal ENA_CLOSE Close enabled 1=Enabled
CTRL.ESXSWI1
3502 218.14 .BlkOpn.stVal BLK_OPEN Open blocked 1=Blocked
3503 218.15 .mcd
Table continues on next page
Section 2 1MRS757057 B
Modbus data mappings
38 REU615
Point List Manual