2.3.2.9 LD0.CMMXU1 Phase current measurements (1)
Table 85: LD0.CMMXU1 Phase current measurements (1)
RegA Typ Scale IEC 61580 name SA name Description Values
LD0.CMMXU1 Phase current (1)
138 u16 1000 .A.phsA.instCVal.mag I_INST_A - phsA amplitude
0.00..40.0
[xIn]
139 u16 1000 .A.phsB.instCVal.mag I_INST_B - phsB amplitude
0.00..40.0
[xIn]
140 u16 1000 .A.phsC.instCVal.mag I_INST_C - phsC amplitude
0.00..40.0
[xIn]
2.3.2.10 LD0.RESVMMXU1 Residual voltage measurement (1)
Table 86: LD0.RESVMMXU1 Residual voltage measurement (1)
RegA Typ Scale IEC 61580 name SA name Description Values
LD0.RESVMMXU1 Residual voltage (1)
151 u16 1000 .A.res.instCVal.mag U0_INST - amplitude
0.00..4.00
[xUn]
2.3.2.11 LD0.CMSQI1 Sequence of current measurements (1)
Table 87: LD0.CMSQI1 Sequence of current measurements (1)
RegA
Typ Scale IEC 61580 name SA name Description Values
LD0.CMSQI1 Sequence of currents
142 u16 1000 .SeqA.c1.instCVal.mag I1_INST - positive amplitude
0.00..40.0
[xIn]
143 u16 1000 .SeqA.c2.instCVal.mag I2_INST - negative amplitude
0.00..40.0
[xIn]
144 u16 1000 .SeqA.c2.instCVal.mag I3_INST - zero amplitude
0.00..40.0
[xIn]
2.3.2.12 LD0.T2PTTR1 Thermal protection values (2)
Table 88: LD0.T2PTTR1 Thermal protection values (2)
RegA
Typ Scale IEC 61580 name SA name Description Values
LD0.T2PTTR1
163 i16 1 .Tmp.mag TEMP Object temperature
-100.0…
9999.9 [C]
164 u16 1 .TmpRl.mag TEMP_RL Relative temperature
0.00…99.99
[C]
165 u16 1 .TmsOp.stVal THERMLEV_ST Est. time to operate 0...60000 [s]
166 u16 1 .TmsRecEna.stVal THERMLEV_END Est. time to deactivate block 0...60000 [s]
Section 2 1MRS757057 B
Modbus data mappings
48 REU615
Point List Manual