RegA Typ Scale IEC 61580 name SA name Description Values
1941 i32 1 .AvVAr.mag - Reactive power Q (high) -/+ 999,999
1942 - (low word)
1943 i32 1 .AvVA.mag - Apparent power S (high) -/+ 999,999
1944 - (low word)
1945 i16 1000 .AvPF.mag - Power factor -1..1
1946 < reserved > 0
Max values:
1947 i32 1 .MaxW.mag - Active power P (high) -/+ 999,999
1948 - (low word)
1949 i32 1 .MaxVAr.mag - Reactive power Q (high) -/+ 999,999
1950 - (low word)
1951 i32 1 .MaxVA.mag - Apparent power S (high) -/+ 999,999
1952 - (low word)
1953 < reserved > 0
2.3.2.21 LD0.VMSTA1 Voltage demand values (1)
Table 97: LD0.VMSTA1 Voltage demand values (1)
RegA
Typ Scale IEC 61580 name SA name Description Values
LD0.VMSTA1 Demand phase-to-ground
1954 u16 1000 .AvVPhsA.mag U_DMD_A - phsA amplitude 0..4.0 [xUn]
1955 u16 1000 .AvVPhsB.mag U_DMD_B - phsB amplitude 0..4.0 [xUn]
1956 u16 1000 .AvVPhsC.mag U_DMD_C - phsC amplitude 0..4.0 [xUn]
Demand phase-to-phase
1957 u16 1000 .AvVPhsAB.mag U_DMD_AB - phsAB amplitude 0..4.0 [xUn]
1958 u16 1000 .AvVPhsBC.mag U_DMD_BC - phsBC amplitude 0..4.0 [xUn]
1959 u16 1000 .AvVPhsCA.mag U_DMD_CA - phsCA amplitude 0..4.0 [xUn]
Update time stamp See doc.
1960 u16 - - Year - month
1961 u16 - - Day - hour
1962 u16 - - Minute - second
1963 u16 - - Milliseconds
1964 u16 - - Time quality