RegA Typ Scale IEC 61580 name SA name Description Values
2029 u16 1 .FACntRs.stVal Fault arc 2 counter 0…65535
LD0.ARCSARC31
2030 u16 1 .FACntRs.stVal Fault arc 3 counter 0…65535
2.3.2.26 LD0.XRGGIO130 RTD input values
Table 102: LD0.XRGGIO130 RTD input values
RegA Typ Scale IEC 61580 name SA name Description Values
LD0.XRGGIO130
2031 i16 1 .AnIn1.mag AI_VAL1 RTD input 1 in ohms -/+ 10000.00
2032 i16 1 .AnIn2.mag AI_VAL2 RTD input 2 in ohms -/+ 10000.00
2033 i16 1 .AnIn3.mag AI_VAL3 RTD input 3 in ohms -/+ 10000.00
2034 i16 1 .AnIn4.mag AI_VAL4 RTD input 4 in ohms -/+ 10000.00
2035 i16 1 .AnIn5.mag AI_VAL5 RTD input 5 in ohms -/+ 10000.00
2036 i16 1 .AnIn6.mag AI_VAL6 RTD input 6 in ohms -/+ 10000.00
2037 i16 1 .AnIn7.mag AI_VAL7 RTD input 7 in ohms -/+ 10000.00
2038 i16 1 .AnIn8.mag AI_VAL8 RTD input 8 in ohms -/+ 10000.00
2.3.2.27 LD0.PEMMTR1 Three-phase energy measurements
Table 103: LD0.PEMMTR1 Three-phase energy measurements
RegA
Typ Scale IEC 61580 name SA name Description Values
LD0.PEMMTR1
2040 u32 1 .SupWh.actVal Reverse active energy (high)
0..1E10
[kWh]
2041 .SupWh.actVal (low word)
2042 u32 1 .SupVArh.actVal Reverse reactive energy (high)
0..1E10
[kVAr]
2043 .SupVArh.actVal (low word)
2044 u32 1 .DemWh.actVal Forward active energy (high)
0..1E10
[kWh]
2045 .DemWh.actVal (low word)
2046 u32 1 .DemVArh.actVal Forward reactive energy (high)
0..1E10
[kVAr]
2047 .DemVArh.actVal (low word)