2.3.2.39 IED Real-time clock (in local time mode) - read and write (synchronize)
Table 115: IED Real-time clock (in local time mode) - read and write (synchronize)
RegA Typ Scale IEC 61580 name SA name Description Values
9201 Control register
0..2 (see
doc.)
9202 Year 2000..2999
9203 Month 1..12
9204 Day 1..31
9205 Hour 0..23
9206 Minute 0..59
9207 Second 0..59
9208 Millisecond 0…999
2.3.2.40 IED real-time clock (in UTC time mode) - read and write (synchronize)
Table 116: IED real-time clock (in UTC time mode) - read and write (synchronize)
RegA Typ Scale IEC 61580 name SA name Description Values
9211 Control register
0..2 (see
doc.)
9212 Year 2000..2999
9213 Month 1..12
9214 Day 1..31
9215 Hour 0..23
9216 Minute 0..59
9217 Second 0..59
9218 Millisecond 0…999
2.3.2.41 Time and reason for latest IED reset
Table 117: Time and reason for latest IED reset
RegA
Typ Scale IEC 61580 name SA name Description Values
9221 u16 1 Year 2000..2999
9222 u16 1 Month 1..12
9223 u16 1 Day 1..31
9224 u16 1 Hour 0..23
9225 u16 1 Minute 0..59
9226 u16 1 Second 0..59
9227 u16 1 Millisecond 0…999
9228 u16 1 Reset reason
Table continues on next page
Section 2 1MRS757057 B
Modbus data mappings
58 REU615
Point List Manual