RegA Typ Scale IEC 61580 name SA name Description Values
9359 u16 1 Data object ID2 see doc.
9360 u16 1 Event data value 1 see doc.
9361 u16 1 Event data value 2 see doc.
2.3.2.44 Fault record structure header
Table 120: Fault record structure header
RegA Typ Scale IEC 61580 name SA name Description Values
Selection write:
9401 i16 1 - Read selection -99…3
Record data header:
9402 u16 1 - Record sequence num 0..65535
9403 u16 1 - Unread records left 0..99
Timestamp of record
9404 u16 1 - Year, month Year/Month
9405 u16 1 - Day, hour Day/Hour
9406 u16 1 - Minute, second Min/Sec
9407 u16 1 - Millisecond Millisecond
9408 u16 1 - Timestamp quality see doc.
LD0.FLTMSTA1 Fault record data
9409 u32 1 .OpCnt.stVal - Fault record number (high) 0..999999
9410 - (low word)
9411 i16 1 .ProFnc.stVal - Protection function -32768..3276
7
9412 u16 100 .StrDur.mag - Start duration 0..100.00 [%]
9413 u32 1000 .OpTm.mag - Operate time [ms] (high) 0..999999.99
9
9414 - (low word)
9415 u16 1 .ActSG.stVal - Active setting group 1..6
9416 u16 1 .ShotPntr.stVal - AR shot pointer value 0..7
9417 u16 < reserved > 0
9418 u16 < reserved > 0
9419 u16 < reserved > 0
9420 u16 < reserved > 0
9421 u16 < reserved > 0
1MRS757057 B Section 2
Modbus data mappings
REU615 63
Point List Manual