EasyManua.ls Logo

ABB Relion 615 series - LD0.SRGAPC2 Reset SRGAPC2 Generic Flip-Flops; LD0.SPCGGIO1 Multipurpose Binary Outputs (1)

ABB Relion 615 series
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2.3.3.10 LD0.SRGAPC2 Reset SRGAPC2 generic flip-flops
Table 132: LD0.SRGAPC2 Reset SRGAPC2 generic flip-flops
0xA CS IEC 61580 name SA name Description Values
LD0.SRGAPC2
2104 4.08 .Rs1.Oper.ctlVal Reset flip-flop 1 1=Reset
2105 4.09 .Rs2.Oper.ctlVal Reset flip-flop 2 1=Reset
2106 4.10 .Rs3.Oper.ctlVal Reset flip-flop 3 1=Reset
2107 4.11 .Rs4.Oper.ctlVal Reset flip-flop 4 1=Reset
2108 4.12 .Rs5.Oper.ctlVal Reset flip-flop 5 1=Reset
2109 4.13 .Rs6.Oper.ctlVal Reset flip-flop 6 1=Reset
2110 4.14 .Rs7.Oper.ctlVal Reset flip-flop 7 1=Reset
2111 4.15 .Rs8.Oper.ctlVal Reset flip-flop 8 1=Reset
2.3.3.11 LD0.SPCGGIO1 Multipurpose binary outputs (1)
The binary outputs may be configured either as pulse- or persistent-type outputs.
Pulse-type outputs are triggered with the write value "1". Persistent-type outputs
can be written with both "1" and "0" values. The persistent type is the same as the
toggled mode on LHMI and WHMI.
Table 133: LD0.SPCGGIO1 Multipurpose binary outputs (1)
0xA
CS IEC 61580 name SA name Description Values
LD0.SPCGGIO1
2112 5.00 .SPCS01.ctlVal Output 1 control 0/1=Off/On
2113 5.01 .SPCS02.ctlVal Output 2 control 0/1=Off/On
2114 5.02 .SPCS03.ctlVal Output 3 control 0/1=Off/On
2115 5.03 .SPCS04.ctlVal Output 4 control 0/1=Off/On
2116 5.04 .SPCS05.ctlVal Output 5 control 0/1=Off/On
2117 5.05 .SPCS06.ctlVal Output 6 control 0/1=Off/On
2118 5.06 .SPCS07.ctlVal Output 7 control 0/1=Off/On
2119 5.07 .SPCS08.ctlVal Output 8 control 0/1=Off/On
2120 5.08 .SPCS09.ctlVal Output 9 control 0/1=Off/On
2121 5.09 .SPCS10.ctlVal Output 10 control 0/1=Off/On
2122 5.10 .SPCS11.ctlVal Output 11 control 0/1=Off/On
2123 5.11 .SPCS12.ctlVal Output 12 control 0/1=Off/On
2124 5.12 .SPCS13.ctlVal Output 13 control 0/1=Off/On
2125 5.13 .SPCS14.ctlVal Output 14 control 0/1=Off/On
2126 5.14 .SPCS15.ctlVal Output 15 control 0/1=Off/On
2127 5.15 .SPCS16.ctlVal Output 16 control 0/1=Off/On
Section 2 1MRS757057 B
Modbus data mappings
68 REU615
Point List Manual

Table of Contents

Other manuals for ABB Relion 615 series

Related product manuals