2.3.3.12 LD0.SPCGGIO2 Multipurpose binary outputs (2)
The binary outputs may be configured either as pulse- or persistent-type outputs.
Pulse-type outputs are triggered with the write value "1". Persistent-type outputs
can be written with both "1" and "0" values. The persistent type is the same as the
toggled mode on LHMI and WHMI.
Table 134: LD0.SPCGGIO2 Multipurpose binary outputs (2)
0xA CS IEC 61580 name SA name Description Values
LD0.SPCGGIO2
2128 6.00 .SPCS01.ctlVal Output 1 control 0/1=Off/On
2129 6.01 .SPCS02.ctlVal Output 2 control 0/1=Off/On
2130 6.02 .SPCS03.ctlVal Output 3 control 0/1=Off/On
2131 6.03 .SPCS04.ctlVal Output 4 control 0/1=Off/On
2132 6.04 .SPCS05.ctlVal Output 5 control 0/1=Off/On
2133 6.05 .SPCS06.ctlVal Output 6 control 0/1=Off/On
2134 6.06 .SPCS07.ctlVal Output 7 control 0/1=Off/On
2135 6.07 .SPCS08.ctlVal Output 8 control 0/1=Off/On
2136 6.08 .SPCS09.ctlVal Output 9 control 0/1=Off/On
2137 6.09 .SPCS10.ctlVal Output 10 control 0/1=Off/On
2138 6.10 .SPCS11.ctlVal Output 11 control 0/1=Off/On
2139 6.11 .SPCS12.ctlVal Output 12 control 0/1=Off/On
2140 6.12 .SPCS13.ctlVal Output 13 control 0/1=Off/On
2141 6.13 .SPCS14.ctlVal Output 14 control 0/1=Off/On
2142 6.14 .SPCS15.ctlVal Output 15 control 0/1=Off/On
2143 6.15 .SPCS16.ctlVal Output 16 control 0/1=Off/On
2.3.3.13 CTRL.DCCSWI1 Disconnector (1) control
Table 135: CTRL.DCCSWI1 Disconnector (1) control
0xA
CS IEC 61580 name SA name Description Values
CTRL.DCCSWI1
2144 7.00 .Pos.Oper.ctlVal Select open 1=Select
2145 7.01 .Pos.Oper.ctlVal Select close 1=Select
2146 7.02 .Pos.Oper.ctlVal Cancel selection 1=Cancel
2147 7.03 .Pos.Oper.ctlVal Execute selection 1=Execute
2148 7.04 .Pos.Oper.ctlVal Direct open 1=Open
2149 7.05 .Pos.Oper.ctlVal Direct close 1=Close