Table 2: Indications and controls
IEC 61850 name AFL-Common SA name Description DPI value FUN INF In Use ASDU GI Coding
Device function type - standard, all variants
LD0.DARREC1.AROn.stVal - Autorecloser state 10=AR On, 01=AR Off 0 16 1 1 1 1
LD0.LLN0.LEDRs1.ctlVal - LED reset 10=Reset indications and alarm LEDs 0 19 1 20 0 1
LD0.LLN0.Beh.stVal (Test mode) - Test mode 10=Test mode ON, 01=Test mode
OFF
0 21 1 1 1 1
LD0.I3CGGIO1.ActSG.ctlVal - Parameter setting group 1 10=Setting group 1 in use 0 23 1 1,20 1 1
LD0.I3CGGIO1.ActSG.ctlVal - Parameter setting group 2 10=Setting group 2 in use 0 24 1 1,20 1 1
LD0.I3CGGIO1.ActSG.ctlVal - Parameter setting group 3 10=Setting group 3 in use 0 25 1 1,20 1 1
LD0.I3CGGIO1.ActSG.ctlVal - Parameter setting group 4 10=Setting group 4 in use 0 26 1 1,20 1 1
LD0.I3CGGIO1.ActSG.ctlVal - Parameter setting group 5 10=Setting group 5 in use 0 27 1 1,20 1 1
LD0.I3CGGIO1.ActSG.ctlVal - Parameter setting group 6 10=Setting group 6 in use 0 28 1 1,20 1 1
LD0.TCSSCBR1.CirAlm.stVal TCSSCBR1.ALARM Trip circuit 1 alarm 10=TCS1 alarm 0 36 1 1 1 1
LD0.LEDPTRC1.Op.general - Global operate 10=Operate (LEDPTRC) 0 68 1 2 0 1
LD0.LEDPTRC1.Str.general - Global start 10=Start (LEDPTRC) 0 84 1 2 1 1
LD0.DARREC1.SucRec.stVal DARREC1.SUC_RECL Successful reclose status 10=Successful reclose 0 128 1 1 0 1
LD0.DARREC1.InInhRec.stVal - Inhibit reclose (status) 10=Reclose inhibit 0 130 1 1 1 1
Device function type - private, all variants
LD0.TRPPTRC1.Op.general - TRPTRC1 input signal 10=Input signal ON 10 1 1 2 0 1
LD0.TRPPTRC1.Tr.general - TRPTRC1 trip output signal 10=Trip output signal ON 10 2 1 2 0 1
LD0.TRPPTRC2.Op.general - TRPTRC2 input signal 10=Input signal ON 10 3 1 2 0 1
LD0.TRPPTRC2.Tr.general - TRPTRC2 trip output signal 10=Trip output signal ON 10 4 1 2 0 1
CTRL.LLN0.Loc.stVal - Local/Remote state 10=Local, 01=Remote 10 10 1 1 1 1
CTRL.LLN0.LocRem.Station - Station state 10=Station ON, 01=OFF 10 11 1 1 1 1
LD0.LLN0.RecRs.ctlVal - Reset all data 10=Reset all data 10 19 1 20 0 1
LD0.LLN0.LEDRs2.ctlVal - Reset alarm LEDs 10=Reset alarm LEDs only 10 21 1 20 0 1
LD0.TCSSCBR2.CirAlm.stVal TCSSCBR2.ALARM Trip circuit 2 alarm 10=TCS2 alarm 10 36 1 1 1 1
DR.RDRE1.RcdTrg.ctlVal - Trig DR recording 10=External DR trig 10 41 1 20 0 1
DR.RDRE1.MemClr.ctlVal - Clear DR memory 10=Clear memory 10 42 1 20 0 1
LD0.CMSTA1.RecRs.ctlVal - Reset CMMXU1 max.demands 10=Reset max values 10 45 1 20 0 1
Multipurpose inputs (all variants)
LD0.MVGAPC1.Q1.stVal - MVGAPC1 input 1 signal 10=Input ON, 01=OFF 11 1 0 1 1 1
LD0.MVGAPC1.Q2.stVal - MVGAPC1 input 2 signal 10=Input ON, 01=OFF 11 2 0 1 1 1
LD0.MVGAPC1.Q3.stVal - MVGAPC1 input 3 signal 10=Input ON, 01=OFF 11 3 0 1 1 1
LD0.MVGAPC1.Q4.stVal - MVGAPC1 input 4 signal 10=Input ON, 01=OFF 11 4 0 1 1 1
LD0.MVGAPC1.Q5.stVal - MVGAPC1 input 5 signal 10=Input ON, 01=OFF 11 5 0 1 1 1
LD0.MVGAPC1.Q6.stVal - MVGAPC1 input 6 signal 10=Input ON, 01=OFF 11 6 0 1 1 1
LD0.MVGAPC1.Q7.stVal - MVGAPC1 input 7 signal 10=Input ON, 01=OFF 11 7 0 1 1 1
LD0.MVGAPC1.Q8.stVal - MVGAPC1 input 8 signal 10=Input ON, 01=OFF 11 8 0 1 1 1
Table continues on next page
Section 2 1MRS756712 C
IEC 60870-5-103 data mappings
14 REF615
Point List Manual