IEC 61850 name AFL-Common SA name Description DPI value FUN INF In Use ASDU GI Coding
LD0.SSCBR1.ClsAlm.stVal SSCBR1.TRV_T_CL_ALM Close travel time exceeded 10=Close travel time alarm 242 102 0 1 0 1
LD0.SSCBR1.SprChaAlm.stVal SSCBR1.SPR_CHR_ALM Spring charging time exceeded 10=Spring charging time alarm 242 103 0 1 0 1
LD0.SSCBR1.OpNumAlm.stVal SSCBR1.OPR_ALM Num of CB operations alarm 10=CB operations alarm 242 104 0 1 0 1
LD0.SSCBR1.OpNumLO.stVal SSCBR1.OPR_LO Num of CB operations lockout limit 10=CB operations lockout alarm 242 105 0 1 0 1
LD0.SSCBR1.LonTmAlm.stVal SSCBR1.MON_ALM CB 'not operated for long time'
alarm
10=CB unactive alarm 242 106 0 1 0 1
LD0.SSCBR1.PresAlm.stVal SSCBR1.PRES_ALM Pressure below alarm level 10=Low pressure alarm 242 107 0 1 0 1
LD0.SSCBR1.PresLO.stVal SSCBR1.PRES_LO Pressure below lockout level 10=Low pressure lockout alarm 242 108 0 1 0 1
LD0.SSCBR1.APwrAlm.stVal SSCBR1.IPOW_ALM Acc. currents power (Iyt),alarm
limit
10=Iyt alarm 242 109 0 1 0 1
LD0.SSCBR1.APwrLO.stVal SSCBR1.IPOW_LO Acc. currents power (Iyt),lockout
limit
10=Iyt lockout alarm 242 110 0 1 0 1
LD0.SSCBR1.CBLifAlm.stVal SSCBR1.CB_LIFE_ALM Remaining life of CB exceeded
alarm limit
10=CB life alarm 242 111 0 1 0 1
Disconnector positions, FE02,04,05,06,07
CTRL.DCSXSWI1.Pos.stVal DCSXSWI1.POSITION Disconnector 1 position 10=Close;01=Open;00=Intermediate;
11=Error
253 1 1 1 1 2
CTRL.DCSXSWI2.Pos.stVal DCSXSWI2.POSITION Disconnector 2 position 10=Close;01=Open;00=Intermediate;
11=Error
253 2 1 1 1 2
CTRL.DCSXSWI3.Pos.stVal DCSXSWI3.POSITION Disconnector 3 position 10=Close;01=Open;00=Intermediate;
11=Error
253 3 1 1 1 2
CTRL.ESSXSWI1.Pos.stVal ESSXSWI1.POSITION Earth switch position 10=Close;01=Open;00=Intermediate;
11=Error
253 11 1 1 1 2
LHMI alarm LED indications, all variants
LD0.LEDGGIO1.SPCSO1.stVal - LED 1 state 10=LED ON, 01=LED OFF 253 89 1 1 1 1
LD0.LEDGGIO1.SPCSO2.stVal - LED 2 state 10=LED ON, 01=LED OFF 253 90 1 1 1 1
LD0.LEDGGIO1.SPCSO3.stVal - LED 3 state 10=LED ON, 01=LED OFF 253 91 1 1 1 1
LD0.LEDGGIO1.SPCSO4.stVal - LED 4 state 10=LED ON, 01=LED OFF 253 92 1 1 1 1
LD0.LEDGGIO1.SPCSO5.stVal - LED 5 state 10=LED ON, 01=LED OFF 253 93 1 1 1 1
LD0.LEDGGIO1.SPCSO6.stVal - LED 6 state 10=LED ON, 01=LED OFF 253 94 1 1 1 1
LD0.LEDGGIO1.SPCSO7.stVal - LED 7 state 10=LED ON, 01=LED OFF 253 95 1 1 1 1
LD0.LEDGGIO1.SPCSO8.stVal - LED 8 state 10=LED ON, 01=LED OFF 253 96 1 1 1 1
LD0.LEDGGIO1.SPCSO9.stVal - LED 9 state 10=LED ON, 01=LED OFF 253 97 1 1 1 1
LD0.LEDGGIO1.SPCSO10.stVal - LED 10 state 10=LED ON, 01=LED OFF 253 98 1 1 1 1
LD0.LEDGGIO1.SPCSO11.stVal - LED 11 state 10=LED ON, 01=LED OFF 253 99 1 1 1 1
Section 2 1MRS756712 C
IEC 60870-5-103 data mappings
22 REF615
Point List Manual