Table 3: Class 2 PRIVATE measurand frames 6 and 7 for REF615 variants FE01,02,03,04
Index IEC 61850 name Description Default scale Frame No6 Frame No7 Comment
1 LD0.CMMXU1.A.phsA.instCVal.mag Phase current A 2.4 x x
2 LD0.CMMXU1.A.phsB.instCVal.mag Phase current B 2.4 x x
3 LD0.CMMXU1.A.phsC.instCVal.mag Phase current C 2.4 x x
4 LD0.RESCMMXU1.A.res.instCVal.mag Residual current 2.4 x x
5 LD0.RESVMMXU1.PhV.res.instCVal.mag Residual voltage 2.4 x x n.a in FE03,04
6 LD0.CSMSQI1.SeqA.c1.instCVal.mag Positive sequence current 2.4 x x
7 LD0.CSMSQI1.SeqA.c2.instCVal.mag Negative sequence current 2.4 x x
8 LD0.CSMSQI1.SeqA.c3.instCVal.mag Zero sequence current 2.4 x x
9 LD0.T1PTTR1.Tmp.mag Temperature of protected object 1000 x x
10 LD0.CMSTA1.AvAmps1.mag Phase current A -average 2.4 x
11 LD0.CMSTA1.AvAmps2.mag Phase current B -average 2.4 x
12 LD0.CMSTA1.AvAmps3.mag Phase current C -average 2.4 x