Table 4: Class 2 PRIVATE measurand frames 6 and 7 for REF615 variant FE05,06,07 and 08
Index IEC 61850 name Description Default scale Frame No6 Frame No7 Comment
1 LD0.CMMXU1.A.phsA.instCVal.mag Phase current A 2.4 x x
2 LD0.CMMXU1.A.phsB.instCVal.mag Phase current B 2.4 x x
3 LD0.CMMXU1.A.phsC.instCVal.mag Phase current C 2.4 x x
4 LD0.RESCMMXU1.A.res.instCVal.mag Residual current 2.4 x x
5 LD0.RESVMMXU1.PhV.res.instCVal.mag Residual voltage 2.4 x x n.a in FE07
6 LD0.CSMSQI1.SeqA.c1.instCVal.mag Positive sequence current 2.4 x x
7 LD0.CSMSQI1.SeqA.c2.instCVal.mag Negative sequence current 2.4 x x
8 LD0.CSMSQI1.SeqA.c3.instCVal.mag Zero sequence current 2.4 x x
9 LD0.T1PTTR1.Tmp.mag Temperature of protected object 1000 x x n.a in FE08
10 LD0.VMMXU1.phV.phsA.cVal.mag Phase-to-ground voltage phase A 2.4 x x
11 LD0.VMMXU1.phV.phsB.cVal.mag Phase-to-ground voltage phase B 2.4 x x
12 LD0.VMMXU1.phV.phsC.cVal.mag Phase-to-ground voltage phase C 2.4 x x
13 LD0.VMMXU1.PPV.phsAB.cVal.mag Phase-to-phase voltage phase AB 2.4 x x
14 LD0.VMMXU1.PPV.phsBC.cVal.mag Phase-to-phase voltage phase BC 2.4 x x
15 LD0.VMMXU1.PPV.phsCA.cVal.mag Phase-to-phase voltage phase CA 2.4 x x
16 LD0.VSMSQI1.SeqA.c1.instCVal.mag Positive sequence voltage 2.4 x x
17 LD0.VSMSQI1.SeqA.c2.instCVal.mag Negative sequence voltage 2.4 x x
18 LD0.VSMSQI1.SeqA.c3.instCVal.mag Zero sequence voltage 2.4 x x
19 LD0.PEMMXU1.TotW.instMag Active power P 1000 x x
20 LD0.PEMMXU1.TotVAr.instMag Reactive power Q 1000 x x
21 LD0.PEMMXU1.TotVA.instMag Apparent power S 1000 x x
22 LD0.PEMMXU1.TotPF.instMag Power factor 1 x x
23 LD0.FMMXU1.Hz.Mag Frequency 100 x x
n.a in
FE05,06,07
24 LD0.CMSTA1.AvAmps1.mag Phase current A -average 2.4 x
25 LD0.CMSTA1.AvAmps2.mag Phase current B -average 2.4 x
26 LD0.CMSTA1.AvAmps3.mag Phase current C -average 2.4 x
Section 2 1MRS756712 C