Section 4 IEC 60870-5-103 parameters and
diagnostics
4.1 Parameter list
The IEC 60870-5-103 parameters can be accessed with PCM600 or via the LHMI path
Configuration/Communication/IEC 60870-5-103/I3C0n.
Some parameters are not visible in the “Basic” setting visibility mode.
To view all parameters use “Advanced” setting visibility mode in the
Parameter Setting tool in PCM600 and LHMI.
Table 14: IEC 60870-5-103 settings
Parameter
Values (Range) Unit Step Default Description
Operation 1=on
5=off
5=off Selects if this protocol instance is enabled
or disabled
Serial port 1=COM 1
2=COM 2
1=COM 1 COM port
Address 1...255 1 1 Unit address
Mapping select 1...2 1 1 Mapping selection
Start delay 0...20 char 1 4 Start frame delay in chars
End delay 0...20 char 1 4 End frame delay in chars
DevFunType 0...255 1 9 Device Function Type
UsrFunType 0...255 1 10 Function type for User Class 2 Frame
UsrInfNo 0...255 1 230 Information Number for User Class2
Frame
Class1Priority 0=Ev High
1=Ev/DR Equal
2=DR High
0=Ev High Class 1 data sending priority relationship
between Events and Disturbance
Recorder data.
Class2Interval
0...86400 s 1 30 Interval in seconds to send class 2
response
Table continues on next page
1MRS759001 A Section 4
IEC 60870-5-103 parameters and diagnostics
615 series 33
Communication Protocol Manual