GUID-E10EE091-CFB9-4278-9FA4-7340C26F5814-ANSI V1 EN
Figure 40: Warning indicating that the values were not written to the
protection relay
If writing is enabled accidentally, click Disable Write. Disable Write
cannot be selected when a value has already been written to the protection
relay. After clicking Write to IED, click either Commit or Reject.
4.2.8 Committing settings
Editable values are stored either in RAM or a nonvolatile flash memory. Values stored in
the flash memory are in effect also after a reboot.
Some parameters have an edit-copy. If editing is cancelled, the values with an edit-copy
are immediately restored to the original value. The values without an edit-copy, such as
string values, are restored to the original value only after a reboot even though the edited
value is not stored in the flash memory.
1. Click Write to IED after editing parameter values to put the values into protection
relay's database for use.
1MAC054853-MB B Section 4
Using the HMI
615 series ANSI 65
Operation Manual