EasyManua.ls Logo

ABB Relion 620 Series - LD0.VSMSQI1 Sequence of Voltage Measurement; LD0.PEMMTR1 Power Measurement and Accumulated Power Values; Protection Functions; LD0.T2 PTTR1 Temperature Protection Values (2)

ABB Relion 620 Series
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2.5.4.8 LD0.VSMSQI1 Sequence of voltage measurement
Table 170: LD0.VSMSQI1 Sequence of voltage measurement
IEC 61850 name SA name Description Values S Arg 1,2,3,4
LD0.VSMSQI1 Sequence of voltages
.SeqV.c1.cVal.mag I1_DB -Positive magnitude
0.00…4.00
[xUn] R 0,4,0,400
.SeqV.c2.cVal.mag I2_DB -Negative magnitude
0.00…4.00
[xUn] R 0,4,0,400
.SeqV.c3.cVal.mag I3_DB -Zero magnitude
0.00…4.00
[xUn] R 0,4,0,400
2.5.4.9 LD0.PEMMTR1 Power measurement and accumulated power values
Table 171: LD0.PEMMTR1 Power measurement and accumulated power values
IEC 61850 name SA name Description Values S Arg 1,2,3,4
LD0.PEMMTR1
.DmdVArh.actVal ER_RV_ACM Forward reactive energy 0…1e10 R 0,1E10,0,1E10
.DmdWh.actVal EA_RV_ACM Forward active energy 0…1e10 R 0,1E10,0,1E10
.SupVArh.actVal ER_FWD_ACM Reverse reactive energy 0…1e10 R 0,1E10,0,1E10
.SupWh.actVal EA_FWD_ACM Reverse active energy 0…1e10 R 0,1E10,0,1E10
.TotPF.instMag PF_INST Average power factor -1…1 R -1,1,-100,100
.TotW.instMag P_INST Active power 0…999999 R 0,999999,0,999999
.TotVA.instMag S_INST Apparent power 0…999999 R 0,999999,0,999999
.TotVAr.instMag Q_INST Reactive power 0…999999 R 0,999999,0,999999
2.5.5 Protection functions
2.5.5.1 LD0.T2PTTR1 Temperature protection values (2)
Table 172: LD0.T2PTTR1 Temperature protection values (2)
IEC 61850 name
SA name Description Values S Arg 1,2,3,4
LD0.T2PTTR1
.Tmp.mag - Object temperature -100…9999.9 R -100,9999.9.0,-1000,99999
.TmpRl.mag - Relative temperature 0…99.9 R 0,99.9,0,999
Section 2 1MRS757660 A
DNP3 data mappings
68 RET620
Point List Manual

Table of Contents