EasyManua.ls Logo

ABB Relion 620 Series - Connecting; Required Tools; Connecting Wires; Connecting Ring-Lug Type Wires

ABB Relion 620 Series
69 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5 Connecting
5.1 Required tools
Only use a screwdriver and insert bits for Phillips (PH 2) cross-recessed head screws
when handling CT/ VT terminals of screw-compression type.
A
B
A Max. ø5.5 mm
B Max. ø5 mm
Figure 28: Screwdriver for CT/VT terminals of screw-compression type
A
A Min. 15 mm
Figure 29: Insert bits for CT/VT terminals of screw-compression type
5.2 Connecting wires
All connections are made on the rear of the case. No soldering is needed.
Open the screw-compression type terminals before inserting any wires. By
default the terminals are closed at the time of delivery.
Use fine wire in door mounting.
See the application manual for product-specific connection diagrams.
5.2.1 Connecting ring-lug type wires
Ring-lug type insulated terminal can be used for signal connector X120 for REF620
and REM620, and both X115 and X120 for RET620. The maximum outside diameter
for the M4 ring-lug type terminals is 9 mm.
Connecting
1MRS757641 G
44 620 series
Installation Manual

Table of Contents

Other manuals for ABB Relion 620 Series