3.4.2 Device identification
3.4.2.1 Device function type
The IEC 60870-5-103 standard requires that an IED is identified as a certain Device
type. The standard has only the following single functional device types:
128 distance protection
160 overcurrent protection device
176 transformer differential protection
192 line differential protection
Since the IEDs are multifunctional, the Device type is set to the private function type
value 9 as default. However, if this definition would cause incompatibility with some
client systems, the definition can be changed through the DevFunType n parameter.
The value in DevFunType n is automatically assigned to all IEC 60870-5-103 data
points that have their function type defined as 0. The user has to assure that no similar
IEC 60870-5-103 point definitions already exist with the same function type and
information number.
3.4.2.2 Device identification code
The device identification information for the IED consists of three parts.
Compatibility level (COL) = 2
Eight character ASCII ID string
Internal code = 4 octets
The ASCII string consists of eight characters, for example, 620FE201.
6 2 0 F E 2 0 1
6 1 5 T E 0 8_
Series (615, 610, 620..)
Device type (REF, RET, REM..)
Region (E=IEC, A=ANSI)
Variant (up to 3 digit number,
padding space (_) characters 20H
added to the end if needed)
GUID-0B5D1BA1-7F2F-4BF3-82C6-75842001B2A4 V1 EN
Figure 3: Examples of device identification codes