If the
Auto lockout reset
setting is not in use, the lockout can be released
only with the
RecRs
parameter.
The AR function can go to lockout for many reasons.
The INHIBIT_RECL input is active.
All shots have been executed and a new initiation is made (final trip).
The time set with the
Auto wait time
parameter expires and the automatic
sequence initiation is not allowed because of a synchronization failure.
The time set with the
Wait close time
parameter expires, that is, the circuit
breaker does not close or the automatic sequence initiation is not allowed due to
a closing failure of the circuit breaker.
A new shot is initiated during the discrimination time.
The time set with the
Max wait time
parameter expires, that is, the master unit
does not release the slave unit.
The frequent operation counter limit is reached and new sequence is initiated.
The lockout is released when the recovery timer elapses.
The protection trip signal has been active longer than the time set with the
Max
wait time
parameter since the shot initiation.
The circuit breaker is closed manually during an autoreclosing sequence and the
manual close mode is FALSE.
9.4.4.6 Protection coordination controller
The PROT_CRD output is used for controlling the protection functions. In several
applications, such as fuse-saving applications involving down-stream fuses,
tripping and initiation of shot 1 should be fast (instantaneous or short-time
delayed). The tripping and initiation of shots 2, 3 and definite tripping time should
be delayed.
In this example, two overcurrent elements PHLPTOC and PHIPTOC are used.
PHIPTOC is given an instantaneous characteristic and PHLPTOC is given a time
delay.
The PROT_CRD output is activated, if the SHOT_PTR value is the same or higher than
the value defined with the
Protection crd limit
setting and all initialization signals
have been reset. The PROT_CRD output is reset under the following conditions:
If the cut-out time elapses
If the reclaim time elapses and the AR function is ready for a new sequence
If the AR function is in lockout or disabled, that is, if the value of the
Protection
crd mode
setting is "AR inoperative" or "AR inop, CB man".
The PROT_CRD output can also be controlled with the
Protection crd mode
setting.
The setting has the following modes:
"no condition": the PROT_CRD output is controlled only with the
Protection crd
limit
setting
"AR inoperative": the PROT_CRD output is active, if the AR function is disabled or
in the lockout state, or if the INHIBIT_RECL input is active
"CB close manual": the PROT_CRD output is active for the reclaim time if the
circuit breaker has been manually closed, that is, the AR function has not issued a
close command
"AR inop, CB man": both the modes "AR inoperative" and "CB close manual" are
effective
1MRS757644 H
Control functions
620 series
Technical Manual
1025