Figure 558: Functional module diagram
9.5.4.1 Voltage and current measurements
The measured voltage must be a phase-to-phase voltage from the regulated
side. Typically, it is the phase-to-phase voltage U_AB from the secondary side of
the power transformer. If the phase voltages are measured, the voltage U_AB is
calculated internally in the IED.
Currents from the secondary side of the power transformer (I_A – I_C) have several
uses.
The highest phase current value is used for overcurrent blocking.
The currents from the secondary side of the power transformer are used for line
drop compensation (average of the connected inputs).