9.5.8 Monitored data
Table 1028: OLATCC Monitored data
Name Type Values (Range) Unit Description
TR0_I_AMPL FLOAT32 0.00...15000.00 A Transmitted cur-
rent magnitude
TR0_I_ANGL FLOAT32 -180.00...180.00 deg Transmitted cur-
rent angle
U_MEAS FLOAT32 0.00...5.00 xUn Phase-to-phase
voltage, average
filtered
ANGL_UA_IA FLOAT32 -180...180 deg Measured angle
value between
phase A voltage
and current
TIMER_STS Enum
0=Timer off
1=Lower timer1
on
2=Raise timer1
on
3=Lower timer2
on
4=Raise timer2
on
5=Fast lower T
on
Timer T1, T2 or
fast lower timer
active
OPR_MODE_STS Enum
0=Not in use
1=Manual
2=Auto single
3=Auto master
4=Auto follower
5=MCC
6=NRP
The acting op-
eration mode
of the function
block
U_CTL FLOAT32 0.000...3.000 xUn Control voltage,
Up, target volt-
age level
UD_CTL FLOAT32 -2.000...2.000 xUn Voltage differ-
ence between
Measured volt-
age - Control
Voltage: Um - Up
Table continues on the next page
Control functions 1MRS757644 H
1078 620 series
Technical Manual