Table 1045: PHQVVR Group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Reference voltage 10.0...200.0 %Un 0.1 57.7 Reference supply
voltage in %
Voltage dip set 1 10.0...100.0 % 0.1 80.0 Dip limit 1 in % of
reference voltage
VVa dip time 1 0.5...54.0 cycles 0.1 3.0 Voltage variation
dip duration 1
Voltage dip set 2 10.0...100.0 % 0.1 80.0 Dip limit 2 in % of
reference voltage
VVa dip time 2 10.0...180.0 cycles 0.1 30.0 Voltage variation
dip duration 2
Voltage dip set 3 10.0...100.0 % 0.1 80.0 Dip limit 3 in % of
reference voltage
VVa dip time 3 2000...60000 ms 10 3000 Voltage variation
dip duration 3
Voltage swell set 1 100.0...140.0 % 0.1 120.0 Swell limit 1 in % of
reference voltage
VVa swell time 1 0.5...54.0 cycles 0.1 0.5 Voltage variation
swell duration 1
Voltage swell set 2 100.0...140.0 % 0.1 120.0 Swell limit 2 in % of
reference voltage
VVa swell time 2 10.0...80.0 cycles 0.1 10.0 Voltage variation
swell duration 2
Voltage swell set 3 100.0...140.0 % 0.1 120.0 Swell limit 3 in % of
reference voltage
VVa swell time 3 2000...60000 ms 10 2000 Voltage variation
swell duration 3
Voltage Int set 0.0...100.0 % 0.1 10.0 Interruption limit in
% of reference volt-
age
VVa Int time 1 0.5...30.0 cycles 0.1 3.0 Voltage variation
Int duration 1
VVa Int time 2 10.0...180.0 cycles 0.1 30.0 Voltage variation
Int duration 2
VVa Int time 3 2000...60000 ms 10 3000 Voltage variation
interruption dura-
tion 3
VVa Dur Max 100...3600000 ms 100 60000 Maximum voltage
variation duration
1MRS757644 H Power quality measurement functions