Ethernet ports marked with LAN A and LAN B are used with redundant Ethernet
protocols HSR and PRP. The third port without the LAN A or LAN B label is an
interlink port which is used as a redundancy box connector with redundant Ethernet
protocols.
Table 1064: Station bus communication interfaces included in communication
modules
Module ID RJ-45 LC EIA-485 EIA-232 ST
COM0001 1 - - - -
COM0002 - 1 - - -
COM0003 - - 1 - -
COM0005 1 - - - -
COM0006 - 1 - - -
COM0007 - - 1 - -
COM0011 1 - 1 - -
COM0012 - 1 1 - -
COM0013 1 - 1 - -
COM0014 - 1 1 - -
COM0023 1 - 1 1 1
COM0031 3 - - - -
COM0032 1 2 - - 1
COM0033 3 - - - 1
COM0034 2 1 - - 1
COM0037 1 2 - - -
Table 1065: LED descriptions for COM0001-COM0014
LED Connector Description
X1 X1 X1/LAN link status and activity (RJ-45 and LC)
RX1 X5 COM2 2-wire/4-wire receiving activity
TX1 X5 COM2 2-wire/4-wire transmitting activity
RX2 X5 COM1 2-wire receiving activity
TX2 X5 COM1 2-wire transmitting activity
I-B X5 IRIG-B signal activity
1
Depending on the COM module and jumper configuration
1MRS757644 H IED physical connections
620 series
Technical Manual
1179