Function block
Figure 86: Function block
Functionality
The Minimum pulse timer function TPGAPC contains two independent timers. The
function has a settable pulse length (in milliseconds). The timers are used for
setting the minimum pulse length for example, the signal outputs. Once the input is
activated, the output is set for a specific duration using the
Pulse time
setting. Both
timers use the same setting parameter.
Figure 87: A = Trip pulse is shorter than Pulse time setting, B = Trip pulse is longer
than Pulse time setting
Signals
Table 143: TPGAPC Input signals
Name Type Default Description
IN1 BOOLEAN 0=False Input 1 status
IN2 BOOLEAN 0=False Input 2 status
Table 144: TPGAPC Output signals
Name Type Description
OUT1 BOOLEAN Output 1 status
OUT2 BOOLEAN Output 2 status
Settings
Table 145: TPGAPC Non group settings
Parameter Values (Range) Unit Step Default Description
Pulse time 0...60000 ms 1 150 Minimum pulse
time
Basic functions 1MRS757644 H
166 620 series
Technical Manual