Table 230: PHLPTOC Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Minimum operate
time
20...60000 ms 1 20 Minimum operate
time for IDMT
curves
Reset delay time 0...60000 ms 1 20 Reset delay time
Measurement
mode
1=RMS
2=DFT
3=Peak-to-Peak
5=Wide P-to-P
2=DFT Selects used meas-
urement mode
Table 231: PHHPTOC Group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Start value 0.10...40.00 xIn 0.01 0.10 Start value
Start value Mult 0.8...10.0 0.1 1.0 Multiplier for scal-
ing the start value
Time multiplier 0.05...15.00 0.01 1.00 Time multiplier
in IEC/ANSI IDMT
curves
Operate delay time 40...200000 ms 10 40 Operate delay time
Operating curve
type
1=ANSI Ext. inv.
3=ANSI Norm. inv.
5=ANSI Def. Time
9=IEC Norm. inv.
10=IEC Very inv.
12=IEC Ext. inv.
15=IEC Def. Time
17=Programmable
15=IEC Def. Time Selection of time
delay curve type
Table 232: PHHPTOC Group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Type of reset curve
1=Immediate
2=Def time reset
3=Inverse reset
1=Immediate Selection of reset
curve type
Table 233: PHHPTOC Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation Off / On
Num of start pha-
ses
1=1 out of 3
2=2 out of 3
3=3 out of 3
1=1 out of 3 Number of phases
required for oper-
ate activation
Curve parameter A 0.0086...120.0000 1 28.2000 Parameter A for
customer program-
mable curve
Curve parameter B 0.0000...0.7120 1 0.1217 Parameter B for
customer program-
mable curve
Table continues on the next page
Protection functions 1MRS757644 H
252 620 series
Technical Manual