of the value to the phase selection logic. If the ENA_MULT input is active, the
Start
value
setting is multiplied by the
Start value Mult
setting.
The IED does not accept the
Start value
or
Start value Mult
setting if the
product of these settings exceeds the
Start value
setting range.
The start value multiplication is normally done when the inrush detection function
(INRPHAR) is connected to the ENA_MULT input.
Figure 127: Start value behavior with ENA_MULT input activated
Phase selection logic
The phase selection logic detects the faulty phase or phases and controls the timers
according to the set value of the
Num of start phases
setting.
Protection functions
1MRS757644 H
258 620 series
Technical Manual