Figure 150: Operating zones at minimum magnitude levels
Level detector
The measured phase currents are compared phasewise to the set
Start value
. If the
measured value exceeds the set
Start value
,the level detector reports the exceeding
of the value, together with the directional results of that phase, to the phase
selection logic. If the ENA_MULT input is active, the
Start value
setting is multiplied
by the
Start value Mult
setting.
The IED does not accept the
Start value
or
Start value Mult
setting if the
product of these settings exceeds the
Start value
setting range.
The start value multiplication is normally done when the inrush detection function
(INRPHAR) is connected to the ENA_MULT input.
Protection functions
1MRS757644 H
302 620 series
Technical Manual