EFIPTOC Input signals
Table 379: EFIPTOC Input signals
Name Type Default Description
Io SIGNAL 0 Residual current
BLOCK BOOLEAN 0=False Block signal for acti-
vating the blocking
mode
ENA_MULT BOOLEAN 0=False Enable signal for cur-
rent multiplier
EFLPTOC Output signals
Table 380: EFLPTOC Output signals
Name Type Description
OPERATE BOOLEAN Operate
START BOOLEAN Start
EFHPTOC Output signals
Table 381: EFHPTOC Output signals
Name Type Description
OPERATE BOOLEAN Operate
START BOOLEAN Start
EFIPTOC Output signals
Table 382: EFIPTOC Output signals
Name Type Description
OPERATE BOOLEAN Operate
START BOOLEAN Start
4.2.1.9 Settings
EFLPTOC Group settings
Table 383: EFLPTOC Group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Start value 0.010...5.000 xIn 0.005 0.010 Start value
Start value Mult 0.8...10.0 0.1 1.0 Multiplier for scal-
ing the start value
Table continues on the next page
1MRS757644 H Protection functions
620 series
Technical Manual
381