Name Type Values (Range) Unit Description
I_OPER FLOAT32 0.00...40.00 xIn Calculated oper-
ating current
DEFLPDEF Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
Table 423: DEFHPDEF Monitored data
Name Type Values (Range) Unit Description
FAULT_DIR Enum
0=unknown
1=forward
2=backward
3=both
Detected fault
direction
START_DUR FLOAT32 0.00...100.00 % Ratio of start
time / operate
time
DIRECTION Enum
0=unknown
1=forward
2=backward
3=both
Direction infor-
mation
ANGLE_RCA FLOAT32 -180.00...180.00 deg Angle between
operating angle
and characteris-
tic angle
ANGLE FLOAT32 -180.00...180.00 deg Angle between
polarizing and
operating quan-
tity
I_OPER FLOAT32 0.00...40.00 xIn Calculated oper-
ating current
DEFHPDEF Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
1MRS757644 H Protection functions
620 series
Technical Manual
417