P
V
W
( )436
5900
32
2
(Equation 101)
Based on
Equation 102
and
Equation 103
, the need for voltage-dependent resistor is
checked.
U
A
kV
max
= + +
25000
2000
5900 15 75 1 00 74 0( . . ) .
(Equation 102)
˘
( ) .u V V V kV= 2 2 436 74000 436 16 0
(Equation 103)
The voltage-dependent resistor (one for each phase) is needed in this case as the
voltage during the fault is higher than 2 kV.
The leakage current through the VDR at the stabilizing voltage can be available from
the VDR manual, assuming that to be approximately 2 mA at stabilizing voltage
Iu A 0 002.
(Equation 104)
The sensitivity of the protection can be recalculated taking into account the leakage
current through the VDR as per
Equation 105
.
I A A A A
prim
= + + 2000 0 035 10 0 0034 0 002 142( . . . )
(Equation 105)
4.3.5.7 Signals
Table 510: HIAPDIF Input signals
Name Type Default Description
I_A SIGNAL 0 Phase A current
BLOCK BOOLEAN 0=False Block signal for acti-
vating the blocking
mode
Table 511: HIBPDIF Input signals
Name
Type Default Description
I_B SIGNAL 0 Phase B current
BLOCK BOOLEAN 0=False Block signal for acti-
vating the blocking
mode
1MRS757644 H Protection functions
620 series
Technical Manual
593