Table 512: HICPDIF Input signals
Name Type Default Description
I_C SIGNAL 0 Phase C current
BLOCK BOOLEAN 0=False Block signal for acti-
vating the blocking
mode
Table 513: HIAPDIF Output signals
Name Type Description
OPERATE BOOLEAN Operate
START BOOLEAN Start
Table 514: HIBPDIF Output signals
Name Type Description
OPERATE BOOLEAN Operate
START BOOLEAN Start
Table 515: HICPDIF Output signals
Name Type Description
OPERATE BOOLEAN Operate
START BOOLEAN Start
4.3.5.8 Settings
Table 516: HIAPDIF Group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Operate value 1.0...200.0 %In 1.0 5.0 Operate value, per-
centage of the
nominal current
Minimum operate
time
20...300000 ms 10 20 Minimum operate
time
Table 517: HIAPDIF Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation Off / On
Table 518: HIAPDIF Non group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Reset delay time 0...60000 ms 10 20 Reset delay time
Protection functions 1MRS757644 H
594 620 series
Technical Manual