EasyManua.ls Logo

ABB Relion 620 Series - Page 607

ABB Relion 620 Series
1224 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
I A A A A
prim
= + +
( )
1000 0 020 2 0 0085 0 37. .
(Equation 123)
The power of the stabilizing resistor is calculated as follows.
P
V
W
( )
323
3900
27
2
(Equation 124)
Based on
Equation 112
and
Equation 113
, the need for voltage dependent resistor is
checked.
U
A
kV
max
. . . .=
+ + +
( )
12 770
1000
3900 15 3 1 73 0 10 36 2
(Equation 125)
˘
.u V V V kV=
( )
2 2 323 36200 323 9 6
(Equation 126)
The voltage dependent resistor, one for each phase, is needed in this case because
the voltage during the fault is much higher than 2 kV.
The leakage current through the varistor at the stabilizing voltage can be available
from the varistor manual, assuming that to be approximately 2 mA at stabilizing
voltage.
Iu A 0 002.
(Equation 127)
The sensitivity of the protection can be re-calculated taking into account the
leakage current through the varistor as per
Equation 110
.
I A A A A
prim
= + +
( )
1000 0 020 2 0 0085 0 002 39. . .
(Equation 128)
4.3.6.8 Signals
Table 532: MHZPDIF Input signals
Name Type Default Description
ID_A REAl 0.0 Differential current
amplitude (DFT)
phase A
ID_B REAL 0.0 Differential current
amplitude (DFT)
phase B
Table continues on the next page
1MRS757644 H Protection functions
620 series
Technical Manual
607

Table of Contents

Other manuals for ABB Relion 620 Series

Related product manuals