Parameter Values (Range) Unit Step Default Description
UR retries 0...65535 1 3 Unsolicited retries before
switching to UR offline mode
UR TO 0...65535 ms 1 5000 Unsolicited response timeout
UR offline interval 0...65535 min 1 15 Unsolicited offline interval
UR Class 1 Min events 0...999 1 2 Min number of class 1 events
to generate UR
UR Class 1 TO 0...65535 ms 1 50 Max holding time for class 1
events to generate UR
UR Class 2 Min events 0...999 1 2 Min number of class 2 events
to generate UR
UR Class 2 TO 0...65535 ms 1 50 Max holding time for class 2
events to generate UR
UR Class 3 Min events 0...999 1 2 Min number of class 3 events
to generate UR
UR Class 3 TO 0...65535 ms 1 50 Max holding time for class 3
events to generate UR
Legacy master UR
1=Disable
2=Enable
1=Disable Legacy DNP master unsolici-
ted mode support. When en-
abled relay does not send ini-
tial unsolicited message.
Legacy master SBO
1=Disable
2=Enable
1=Disable Legacy DNP Master SBO se-
quence number relax enable
Default Var Obj 01
1=1:BI
2=2:BI&status
1=1:BI 1=BI; 2=BI with status.
Default Var Obj 02
1=1:BI event
2=2:BI event&time
2=2:BI event&time 1=BI event; 2=BI event with
time.
Default Var Obj 03
1=1:DBI
2=2:DBI&status
1=1:DBI 1=DBI; 2=DBI with status.
Default Var Obj 04
1=1:DBI event
2=2:DBI event&time
2=2:DBI event&time 1=DBI event; 2=DBI event with
time.
Default Var Obj 20
1=1:32bit Cnt
2=2:16bit Cnt
5=5:32bit Cnt no-
flag
6=6:16bit Cnt no-
flag
2=2:16bit Cnt 1=32 bit counter; 2=16 bit
counter; 5=32 bit counter
without flag; 6=16 bit counter
without flag.
Default Var Obj 21
1=1:32bit FrzCnt
2=2:16bit FrzCnt
5=5:32bit
FrzCnt&time
6=6:16bit
FrzCnt&time
9=9:32bit FrzCnt
noflag
10=10:16bit FrzCnt
noflag
6=6:16bit
FrzCnt&time
1=32 bit frz counter; 2=16 bit
frz counter; 5=32 bit frz coun-
ter with time; 6=16 bit frz
counter with time; 9=32 bit frz
counter without flag;10=16 bit
frz counter without flag.
Default Var Obj 22
1=1:32bit Cnt evt
2=2:16bit Cnt evt
5=5:32bit Cnt
evt&time
6=6:16bit Cnt
evt&time
6=6:16bit Cnt
evt&time
1=32 bit counter event; 2=16
bit counter event; 5=32 bit
counter event with time; 6=16
bit counter event with time.
Table continues on the next page
1MRS757644 H Basic functions
620 series
Technical Manual
65