EasyManua.ls Logo

ABB Relion 620 Series - Page 777

ABB Relion 620 Series
1224 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Figure 409: The behavior of the IDMT timer and the output ST_OVLOD
The ST_DUR_OVLOD output indicates the percentage ratio of the start situation and
the operation time in the Timer 1 module and is available in the monitored data
view.
The Timer 1 module is internally blocked for one second after the
capacitor bank is connected by detecting the rising edge of the
CB_CLOSED signal. The CB_CLOSED signal is True when the CB position
is closed.
Alarm level detector
The Alarm level detector compares I_PEAK_INT_x value to
Alarm start value
. If the
phase or phases in which I_PEAK_INT_x exceeds the setting matches the
Num of
start phases
setting, the Alarm level detector module activates the Timer 2 module.
The
Num of start phases
setting is a common setting for both Operate
level detector and Alarm level detector.
Timer 2
The Timer 2 characteristics are according to Definite Time (DT) .When the operation
timer has reached the value of
Alarm delay time
, the ALARM output is activated.
If a drop-off situation happens, the timer is reset.
The Timer 2 module is internally blocked for one second after the
capacitor bank is connected by detecting the rising edge of the
1MRS757644 H Protection functions
620 series
Technical Manual
777

Table of Contents

Other manuals for ABB Relion 620 Series

Related product manuals