4.12.2.6 Signals
Table 751: CUBPTOC Input signals
Name Type Default Description
I_UNB REAL 0.0 Capacitor bank unbal-
ance current
I_A REAL 0.0 Phase A current
BLOCK BOOLEAN 0=False Block signal for acti-
vating the blocking
mode
Table 752: CUBPTOC Output signals
Name Type Description
OPERATE BOOLEAN Operate
START BOOLEAN Start
ALARM BOOLEAN Alarm
4.12.2.7 Settings
Table 753: CUBPTOC Group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Alarm mode
1=Normal
2=Element counter
1=Normal Mode of operation
for Alarm stage
Start value 0.01...1.00 xIn 0.01 0.10 Start value
Alarm start value 0.01...1.00 xIn 0.01 0.05 Alarm start value
Time multiplier 0.05...15.00 0.01 1.00 Time multiplier
in IEC/ANSI IDMT
curves
Operating curve
type
1=ANSI Ext. inv.
2=ANSI Very inv.
3=ANSI Norm. inv.
4=ANSI Mod. inv.
5=ANSI Def. Time
6=L.T.E. inv.
7=L.T.V. inv.
8=L.T. inv.
9=IEC Norm. inv.
10=IEC Very inv.
11=IEC inv.
12=IEC Ext. inv.
13=IEC S.T. inv.
14=IEC L.T. inv.
15=IEC Def. Time
17=Programmable
18=RI type
19=RD type
15=IEC Def. Time Selection of time
delay curve type
Table continues on the next page