Parameter Values (Range) Unit Step Default Description
Operate delay time 50...200000 ms 10 5000 Operate delay time
Alarm delay time 50...200000 ms 10 200000 Alarm delay time
Table 754: CUBPTOC Group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Fuse location
1=Internal
2=External
1=Internal Location of capaci-
tor fuse
Element fail limit 1...100 1 3 Element failure lim-
it above which
alarm is active
Natural Comp ena-
ble
0=False
1=True
0=False Enable natural un-
balance compensa-
tion
Table 755: CUBPTOC Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation Off / On
Curve parameter A 0.00860...120.0000
0
1 28.20000 Parameter A for
customer program-
mable curve
Curve parameter B 0.00000...0.71200 1 0.12170 Parameter B for
customer program-
mable curve
Curve parameter C 0.02...2.00 1 2.00 Parameter C for
customer program-
mable curve
Curve parameter E 0.0...1.0 1 1.0 Parameter E for
customer program-
mable curve
Table 756: CUBPTOC Non group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Reset delay time 0...60000 ms 1 20 Reset delay time
Minimum operate
time
20...60000 ms 1 20 Minimum operate
time for IDMT
curves
4.12.2.8 Monitored data
Table 757: CUBPTOC Monitored data
Name
Type Values (Range) Unit Description
START_DUR FLOAT32 0.00...100.00 % Ratio of start
time / operate
time
I_NAT_AMPL FLOAT32 0.00...5.00 xIn Recorded natural
unbalance cur-
rent amplitude
Table continues on the next page
Protection functions 1MRS757644 H
792 620 series
Technical Manual