the High pass filter. The K
th
harmonic component is removed by passing the
High pass filter output through the K
th
harmonic Band stop filter. The magnitude
response of the High pass filter and all the harmonic Band stop filters are shown in
Figure 417
.
Figure 417: Magnitude response of High pass and all the harmonic Band stop filters
Similarly resonance current is calculated in the same way for phase B and phase
C. Resonance currents I_RESO_A, I_RESO_B and I_RESO_C are available in the
monitored data view.
The maximum of the three calculated resonance currents is further considered for
calculation.
I RESONANCE Max I RESO A I RESO B I RESO C_ ( _ _ _ _ _ _= , , )
(Equation 150)
If a capacitor bank is used only for reactive power compensation and
there is no series reactor in a filter branch, the resonance protection is
very important. In this case, the setting
Tuning harmonic Num
should be
set to 1 because the capacitor branch is not tuned for a special frequency
as in tuned filter applications. Even though
Tuning harmonic Num
is set
to 1, the fundamental component is subtracted only once from I
RMS
.
Level detector 1
The maximum calculated resonance current is compared to the set
Alarm start
value
. If the calculated I_RESONANCE exceeds the set
Alarm start value
, the module
sends the enabling signal to the Timer 1 module.
Level detector 2
The maximum calculated resonance current is compared to the set
Start value
. If
the calculated I_RESONANCE exceeds the set
Start value
, this module sends the
enabling signal to the Timer 2 module.