Parameter Values (Range) Unit Step Default Description
Active power Dir
1=Forward
2=Reverse
1=Forward Direction of active
power flow: For-
ward, Reverse
Reactive power Dir
1=Forward
2=Reverse
1=Forward Direction of reac-
tive power flow:
Forward, Reverse
Table 943: PEMMXU Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Forward Wh Initial 0...999999999 1 0 Preset Initial value
for forward active
energy
Reverse Wh Initial 0...999999999 1 0 Preset Initial value
for reverse active
energy
Forward VArh Initial 0...999999999 1 0 Preset Initial value
for forward reac-
tive energy
Reverse VArh Initial 0...999999999 1 0 Preset Initial value
for reverse reactive
energy
8.1.12.5 Monitored data
Table 944: PEMMXU Monitored data
Name Type Values (Range) Unit Description
S-kVA FLOAT32 -999999.9...9999
99.9
kVA Total Apparent
Power
P-kW FLOAT32 -999999.9...9999
99.9
kW Total Active Pow-
er
Q-kVAr FLOAT32 -999999.9...9999
99.9
kVAr Total Reactive
Power
PF FLOAT32 -1.00...1.00 Average Power
factor
RSTACM BOOLEAN
0=False
1=True
Reset of accu-
mulated energy
reading
S_INST FLOAT32 -999999.9...9999
99.9
kVA Apparent power,
magnitude of in-
stantaneous val-
ue
S_DB FLOAT32 -999999.9...9999
99.9
kVA Apparent power,
magnitude of re-
ported value
S_DMD FLOAT32 -999999.9...9999
99.9
kVA Demand value of
apparent power
Table continues on the next page
Measurement functions 1MRS757644 H
962 620 series
Technical Manual