Binary inputs and outputs
Table 11. BIM - Binary input module
Quantity Rated value Nominal range
Binary inputs 16 -
DC voltage, RL 24/30 V
48/60 V
110/125 V
220/250 V
RL ± 20%
RL ± 20%
RL ± 20%
RL ± 20%
Power consumption
24/30 V, 50mA
48/60 V, 50mA
110/125 V, 50mA
220/250 V, 50mA
220/250 V, 110mA
max. 0.05 W/input
max. 0.1 W/input
max. 0.2 W/input
max. 0.4 W/input
max. 0.5 W/input
-
Counter input frequency 10 pulses/s max -
Oscillating signal discriminator Blocking settable 1–40 Hz
Release settable 1–30 Hz
Debounce filter Settable 1–20ms
Maximum 176 binary input channels may
be activated simultaneously with influencing
factors within nominal range.
Table 12. BIM - Binary input module with enhanced pulse counting capabilities
Quantity Rated value Nominal range
Binary inputs 16 -
DC voltage, RL 24/30 V
48/60 V
110/125 V
220/250 V
RL ± 20%
RL ± 20%
RL ± 20%
RL ± 20%
Power consumption
24/30 V
48/60 V
110/125 V
220/250 V
max. 0.05 W/input
max. 0.1 W/input
max. 0.2 W/input
max. 0.4 W/input
-
Counter input frequency 10 pulses/s max -
Balanced counter input frequency 40 pulses/s max -
Oscillating signal discriminator Blocking settable 1–40 Hz
Release settable 1–30 Hz
Maximum 176 binary input channels may
be activated simultaneously with influencing
factors within nominal range.